DocumentCode
836907
Title
Joint Frequency Distributions of Stroke Current Rates of Rise and Crest Magnitude to Transmission Lines
Author
Brown, Gordon W.
Author_Institution
U. S. Energy Research and Development Administration
Issue
1
fYear
1978
Firstpage
53
Lastpage
58
Abstract
Since strike distance is a function of stroke current magnitude, it is shown that the frequency distribution of rates of rise of stroke current to any structure can be readily determined. The most important of these is that for negative first components to transmission lines. For any realistic line configuration, the distribution is approximately log-normal with a mean of 12kA/¿s. The standard deviation of the natural logarithm of the ratio of dI/dt to the mean is approximately 0.55 (i.e., 2 standard deviations from the mean, the rate of rise is 36kA/¿s).
Keywords
Fasteners; Frequency; Power & Energy Society; Power transmission lines; Predictive models; Printing; Research and development; Senior members; Transmission line theory; Transmission lines;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1978.354455
Filename
4181399
Link To Document