• DocumentCode
    837111
  • Title

    Scaling Criteria for Interruption Performance in Gas-Blast Circuit-Breakers

  • Author

    Perkins, J.F.

  • Author_Institution
    Westinghouse Electric Corporation Switchgear Division
  • Issue
    1
  • fYear
    1978
  • Firstpage
    232
  • Lastpage
    241
  • Abstract
    The high cost and complexity of short-circuit interruption testing of gas-blast power circuit-breakers make it essential to use most efficiently results of reduced power development tests in interrupter design. Due to the limited capacity of direct testing stations many EHV-breakers must be evaluated by indirect methods such as synthetic-testing of single interrupter units. The interpretation of synthetic-test data and the effective utilization of reduced power test data in circuit-breaker design can be enhanced by the development of accurate scaling criteria. The present paper demonstrates to what extend scaling of enthalpy-flow, current density, pressure, interruption capability, nozzle area ratio, contact spacing, and shape factors can extend the results of reduced power experimental tests to predict performance at full short-circuit ratings.
  • Keywords
    Circuit testing; Contacts; Costs; Current density; Interrupters; Performance evaluation; Shape; Switchgear; System testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1978.354474
  • Filename
    4181418