Title :
Designing EHV Lines to a Given Outage Rate Simplified Techniques
Author :
Brown, Gordon W.
Author_Institution :
University of Pittsburgh
fDate :
3/1/1978 12:00:00 AM
Abstract :
A simplified method for determining the COF required for a given Switching Surge Performance Level is given. If the surge voltage varies along the line, the line is shown to be equivalent to a shorter line. This shorter line will have a number of towers proportional to the insulation strength standard deviation (¿f/CFO) and inversely proportional to (1-¿), where ¿ is the ratio of switch end to open end voltage. The method is illustrated with examples, including both normal and extreme value distributions of over-voltage. Comparison of the method with exact calculations show no significant differences.
Keywords :
Flashover; Frequency; Insulation; Poles and towers; Power engineering and energy; Power systems; Surges; Switches; Systems engineering and theory; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1978.354495