• DocumentCode
    837453
  • Title

    Dynamic ARC Analysis of Short-Line Fault Tests for Accurate Circuit Breaker Performance Specification

  • Author

    Frost, L.S.

  • Author_Institution
    Westinghouse Research Laboratories
  • Issue
    2
  • fYear
    1978
  • fDate
    3/1/1978 12:00:00 AM
  • Firstpage
    478
  • Lastpage
    484
  • Abstract
    The continuing program of analysis of circuit breaker short-line fault test data has culminated in a practicable method for getting complete performance and circuit information quickly from presently available test data and a simple, time-sharing computer program. A dynamic model of the circuit breaker arc near current zero using both the Cassie and the Mayr differential equations, has been solved by computer including interaction with resistance and capacitance shunts. By expressing the critical cases which just interrupt in terms of voltage and current slope coefficients, the model is fitted to key measurements from the test oscillograms. More precise specification of performance and its dependence on electrical parameters results.
  • Keywords
    Circuit analysis; Circuit analysis computing; Circuit breakers; Circuit faults; Circuit testing; Differential equations; Electric resistance; Information analysis; Performance analysis; Time sharing computer systems;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1978.354508
  • Filename
    4181453