DocumentCode :
838564
Title :
Measurement of Voltage Distribution Phenomena in SF6 Single Pressure Circuit Breaker
Author :
Kobayashi, A. ; Yanabu, S. ; Yamashita, S. ; Tomimuro, S. ; Haginomori, E.
Author_Institution :
High Power Laboratory Hamakawasaki Works Tokyo Shibaura Electric Company Limited
Issue :
4
fYear :
1978
fDate :
7/1/1978 12:00:00 AM
Firstpage :
1304
Lastpage :
1312
Abstract :
Voltage distribution phenomena in the thermal reignition region have been measured with a SF6 single- pressure gas circuit breaker of two-break type. Under test conditions below the limit of interruption ability, the voltage distribution was the same as that determined by the external capacitors. On the other hand, under test conditions in the vicinity of the limit of interruption ability, unbalanced voltage distribution phenomena due to the post arc current were observed.
Keywords :
Capacitors; Circuit breakers; Circuit testing; Current measurement; Ignition; Laboratories; Light scattering; Pressure measurement; Sulfur hexafluoride; Voltage measurement;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1978.354615
Filename :
4181562
Link To Document :
بازگشت