Title :
Interleaved High-Voltage Transformer Windings
Author_Institution :
Westinghouse Electric Corporation
Abstract :
Interleaved-turn high-voltage transformer windings are a useful alternative to continuous disc and layer windings for a wide range of transformer output and voltage ratings. Many configurations have been devised to meet different requirements. This paper reports the discovery that the original and most- commonly-used form of interleaved winding has an unexpectedly large internal oscillatory response to chopped-wave or front-of-wave impulse (lightning surge) voltages. It describes the subsequent development of a less-oscillatory winding which allows smaller insulation clearances for equivalent reliability.
Keywords :
Costs; Interleaved codes; Lightning; Oil insulation; Power transformer insulation; Power transformers; Transformer cores; Voltage; Voltage-controlled oscillators; Windings;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1978.354691