DocumentCode :
839352
Title :
Interleaved High-Voltage Transformer Windings
Author :
van Nuys, R.
Author_Institution :
Westinghouse Electric Corporation
Issue :
5
fYear :
1978
Firstpage :
1946
Lastpage :
1954
Abstract :
Interleaved-turn high-voltage transformer windings are a useful alternative to continuous disc and layer windings for a wide range of transformer output and voltage ratings. Many configurations have been devised to meet different requirements. This paper reports the discovery that the original and most- commonly-used form of interleaved winding has an unexpectedly large internal oscillatory response to chopped-wave or front-of-wave impulse (lightning surge) voltages. It describes the subsequent development of a less-oscillatory winding which allows smaller insulation clearances for equivalent reliability.
Keywords :
Costs; Interleaved codes; Lightning; Oil insulation; Power transformer insulation; Power transformers; Transformer cores; Voltage; Voltage-controlled oscillators; Windings;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1978.354691
Filename :
4181639
Link To Document :
بازگشت