DocumentCode
839373
Title
Torsional Fatigue of Turbine-Generator Shafts Caused by Different Electrical System Faults and Switching Operations
Author
Joyce, John S. ; Kulig, Tadeusz ; Lambrecht, Dietrich
Author_Institution
Allis-Chalmers Power Systems, Inc.
Issue
5
fYear
1978
Firstpage
1965
Lastpage
1977
Abstract
The torsional stresses that occur in large steam turbine- generator shafts due to both planned and unplanned system switching operations are discussed. These operations include routine line switching, reclosing line-to-ground faults by either triple-pole or single-pole breaker operation, reclosing line-to-line and three-phase faults, malsynchronization and load rejection. The calculation of cumulative fatigue of individual turbine-generator shafts from computer-plotted torsional swing traces is explained. The benefits of single-pole breaker operation and of dividing the output of large generators between different electrical systems are briefly mentioned.
Keywords
Circuit faults; Fatigue; Machinery; Power system faults; Power system transients; Senior members; Shafts; Stress; Transient analysis; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1978.354693
Filename
4181641
Link To Document