• DocumentCode
    839373
  • Title

    Torsional Fatigue of Turbine-Generator Shafts Caused by Different Electrical System Faults and Switching Operations

  • Author

    Joyce, John S. ; Kulig, Tadeusz ; Lambrecht, Dietrich

  • Author_Institution
    Allis-Chalmers Power Systems, Inc.
  • Issue
    5
  • fYear
    1978
  • Firstpage
    1965
  • Lastpage
    1977
  • Abstract
    The torsional stresses that occur in large steam turbine- generator shafts due to both planned and unplanned system switching operations are discussed. These operations include routine line switching, reclosing line-to-ground faults by either triple-pole or single-pole breaker operation, reclosing line-to-line and three-phase faults, malsynchronization and load rejection. The calculation of cumulative fatigue of individual turbine-generator shafts from computer-plotted torsional swing traces is explained. The benefits of single-pole breaker operation and of dividing the output of large generators between different electrical systems are briefly mentioned.
  • Keywords
    Circuit faults; Fatigue; Machinery; Power system faults; Power system transients; Senior members; Shafts; Stress; Transient analysis; Voltage;