  • Abstract
    Winding deformation in power transformers can be measured externally using a new frequency response analysis (FRA) method Field experience since 1975, on five separate transformers up to 550 MVA rating, 230kVclassindicatesthatthismethod hasadvantagesover the low voltage impulse (LVI) method as a practical maintenance tool. Results on suspect transformers indicate that benchmark reference data is not always necessary to identify certain kinds of mechanical damage.
  • Keywords
    Capacitance; Circuit testing; Frequency measurement; Frequency response; Instruments; Insulators; Low voltage; Power measurement; Power transformers; US Department of Transportation;