DocumentCode :
839951
Title :
Mathematical Modelling -- A Basis for Bushing Loading Guides
Author :
McNutt, W.J. ; Easley, J.K.
Author_Institution :
General Electric Company
Issue :
6
fYear :
1978
Firstpage :
2393
Lastpage :
2404
Abstract :
A simple mathematical thermal model is proposed as a basis for a bushing loading guide. It is demonstrated to have adequate accuracy for both steady-state and transient bushing hot-spot temperature calculations. Model constants can be derived from a set of "Overload Qualification" tests and recommendations are made for the parameters of significance to these tests. Three possible thermal failure modes are examined to establish a basis for setting a maximum permissible hot-spot temperature during overloads. Limitations on environmental factors which influence the bushing hot-spot temperature are also discussed.
Keywords :
Gaskets; Insulators; Mathematical model; Power transformers; Predictive models; Steady-state; Strontium; Temperature; Testing; Thermal loading;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1978.354746
Filename :
4181695
Link To Document :