• DocumentCode
    842214
  • Title

    Spark Gap Breakdown at EMP Threat Level Rates of Voltage Rise

  • Author

    Trybus, P.R. ; Chodorow, A.M. ; Endsley, D.L. ; Bridge, J.E.

  • Author_Institution
    Mission Research Corporation Albuquerque, New Mexico 87108
  • Volume
    26
  • Issue
    6
  • fYear
    1979
  • Firstpage
    4959
  • Lastpage
    4963
  • Abstract
    Electrical Surge Arrestors (ESAs) are used extensively for lightning and EMP protection on conductors which may be excited by these hostile environments. In-situ measurements of peak pulse voltage were performed at rates of voltage rise from 200 to 2000 kV/¿s on several types of surge arrestors and combinations of spark gaps and filters. These data are presented along with samples of previous measurements. The effects of lead inductance and low impedance loading by the filter input capacitance are illustrated. Experimental results are compared to theoretical predictions of an ESA model used for EMP analyses.
  • Keywords
    Breakdown voltage; Conductors; EMP radiation effects; Filters; Inductance; Lightning; Performance evaluation; Pulse measurements; Spark gaps; Surge protection;
  • fLanguage
    English
  • Journal_Title
    Nuclear Science, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9499
  • Type

    jour

  • DOI
    10.1109/TNS.1979.4330256
  • Filename
    4330256