• DocumentCode
    843052
  • Title

    Measured data transmission performance for AM broadcast-VHF radio distribution automation communication system

  • Author

    Anderson, Harry R.

  • Author_Institution
    H.R. Anderson & Associates Inc., Eugene, OR, USA
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    1/1/1989 12:00:00 AM
  • Firstpage
    82
  • Lastpage
    89
  • Abstract
    The measured data transmission signaling performance for an AM broadcast (outbound) VHF radio (inbound) two-way distribution automation system is presented. The performance data are presented as a function of signal level, transmission path length and time of day. The outbound link, which uses inaudible low-speed phase modulation of the carrier of a standard AM broadcast station, demonstrated overall average signaling success rates of better than 99% in operational transceiver units. For the 154 MHz VHF return link, which used unconventional low-speed amplitude modulation resolved by a real-time FFT detector-receiver, the measured overall signaling success rate averaged about 60%
  • Keywords
    distribution networks; power system computer control; radio systems; telecontrol equipment; 154 MHz; AM broadcast; VHF radio; amplitude modulation; distribution automation; phase modulation; power system telecontrol; radio systems; signal level; signaling performance; transceiver units; transmission path length; Amplitude modulation; Automatic control; Automation; Communication system control; Control systems; Data communication; Phase modulation; Radio broadcasting; System testing; Transceivers;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.19191
  • Filename
    19191