• DocumentCode
    843544
  • Title

    Very fast transients in GIS

  • Author

    Meppelink, J. ; Diederich, K. ; Feser, K. ; Pfaff, W.

  • Author_Institution
    BBC Brown Boveri Ltd., Baden, Switzerland
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • Firstpage
    223
  • Lastpage
    233
  • Abstract
    Different types of very fast transients (VFTs) are classified and their characteristic parameters are summarized based on measurements in a 800 kV SF/sub 6/ gas-insulated pilot installation and 420 kV GIS (gas-insulated switchgear) in service. The electromagnetic field between the enclosure and earth results in a transient enclosure voltage of up to some 10 kV and at the same time in a radiated electromagnetic field from the enclosure with amplitude of some 10 kV/m. The electromagnetic wave guided by the overhead line results in an overvoltage with a multifrequent oscillation of some 10 to 100 kHz, depending on the parameters of the overhead line and the adjacent equipment, e.g. the transformer. The transient enclosure voltage and measures to reduce it are analyzed.<>
  • Keywords
    sulphur compounds; switchgear; transients; 10 kV; 10 to 100 kHz; 420 kV; 800 kV; SF/sub 6/; electromagnetic field; gas-insulated pilot installation; gas-insulated switchgear; multifrequent oscillation; overhead line; transient enclosure voltage; very fast transients; Earth; Electromagnetic fields; Electromagnetic measurements; Electromagnetic scattering; Electromagnetic transients; Gas insulation; Geographic Information Systems; Switchgear; Transient analysis; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.19208
  • Filename
    19208