DocumentCode
844378
Title
Investigations of prestriking and current chopping in medium voltage SF6 rotating arc and vacuum switchgear
Author
Gibbs, J.D. ; Koch, D. ; Malkin, P. ; Cornick, K.J.
Author_Institution
Merlin Gerin, Grenoble, France
Volume
4
Issue
1
fYear
1989
fDate
1/1/1989 12:00:00 AM
Firstpage
308
Lastpage
316
Abstract
Prestriking overvoltages and current chopping levels of SF6 rotating arc switching devices are examined. Experiments have been carried out to determine the effects of circuit configurations on prestriking and current chopping. These results are compared with those of other switching media obtained under identical conditions. The prestriking overvoltages of the contactor were found to be restricted by its high-frequency current interruption capability and dielectric recovery rate. The dielectric recovery profile also restricted the magnitude of subsequent prestrike overvoltages to values smaller than the first transient. Current chopping levels increased with parallel capacitance
Keywords
sulphur compounds; switchgear; vacuum apparatus; SF6 rotating arc switching devices; current chopping levels; dielectric recovery profile; dielectric recovery rate; high-frequency current interruption capability; medium voltage; parallel capacitance; prestriking overvoltages; vacuum switchgear; Circuit breakers; Contacts; Cooling; Insulation; Medium voltage; Sulfur hexafluoride; Surge protection; Switches; Switchgear; Switching circuits;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.19218