Title :
Empirical model of a current-limiting fuse using EMTP
Author :
Petit, André ; St-Jean, Guy ; Fecteau, Gilles
Author_Institution :
Inst. de Recherche d´´Hydro-Quebec, Varennes, Que., Canada
fDate :
1/1/1989 12:00:00 AM
Abstract :
An empirical model is discussed for research on current-limiting (CL) fuses used in distribution system applications. The main characteristic of a CL fuse is that it develops a voltage at its terminals which reduces the amount of energy generated in the protected equipment during a fault. The various stages of fuse operation are modeled using electric components. The model is of limited use, but its simplicity enables a nonexpert to use it without spending months to learn and program a sophisticated model. The model makes it possible to establish which closing angle of source voltage will produce the greatest of I2t, assuming a melting time shorter than a quarter of a cycle. The model can also show how the let-through value of I2t will be influenced by the voltage versus time profile of the fuse voltage. The electromagnetic transient program, EMTP, proved a useful tool for this development
Keywords :
electric fuses; electromagnetic fields; transients; EMTP; current-limiting fuse; distribution system; electromagnetic transient program; empirical model; fault; melting time; Character generation; Circuit faults; Circuit testing; EMTP; Fuses; Protection; Senior members; Switchgear; Transformers; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on