Fault current capability of distribution transformers with under-oil arresters
Author :
Henning, W.R. ; Hernandez, A.D. ; Lien, W.W.
Author_Institution :
RTE Corp., Waukesha, WI, USA
Volume :
4
Issue :
1
fYear :
1989
fDate :
1/1/1989 12:00:00 AM
Firstpage :
405
Lastpage :
412
Abstract :
Fault current withstand capability testing of distribution transformers with under-oil arresters is discussed. The tests performed simulate the effect of an arrester failure under oil within the transformer. Experience with different test methods used to demonstrate withstand capability is described. The advantages of an internally mounted arrester are reviewed, and the effect of an arrester failure is reviewed. The way in which the arrester fails affects the resulting arc energy and peak pressure within the enclosure. The test circuit parameters, the arc energies, and the effects on the transformer are presented. Based on the test data, recommendations are made for current-limiting fuse protection at specific fault current levels and arrester ratings
Keywords :
electric fuses; fault currents; power transformers; surge protection; arc energy; arrester failure; current-limiting fuse protection; distribution transformers; fault-current withstand capability; test circuit parameters; under-oil arresters; Arresters; Circuit testing; Contamination; Fault currents; Fuses; Performance evaluation; Petroleum; Power system protection; Surge protection; Transformers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.19230
Filename :
19230
Link To Document :
بازگشت