Title :
The lightning performance of unshielded steel-structure transmission lines
Author :
Mousa, Abdul M. ; Srivastava, K.D.
Author_Institution :
British Columbia Hydro, Vancouver, BC, Canada
fDate :
1/1/1989 12:00:00 AM
Abstract :
A method is presented for calculating the lightning performance of unshielded steel-structure transmission lines. The method is an adaptation of the Anderson/IEEE method for shielded lines, and it incorporates an algorithm for calculating separate magnitudes and frequency distributions of the strokes to the towers and the strokes to the conductors. The results of applying the method to 230 kV, 500 kV and 765 kV lines are presented, and the effects of voltage class, span and form of striking distance equation are discussed
Keywords :
lightning protection; poles and towers; power overhead lines; transmission networks; 230 kV; 500 kV; 765 kV; Anderson/IEEE method; lightning performance; striking distance; towers; unshielded steel-structure transmission lines; Circuits; Flashover; Frequency; Insulation; Lightning; Poles and towers; Power transmission lines; Transmission lines; Voltage; Wires;
Journal_Title :
Power Delivery, IEEE Transactions on