Power factor compensation at buses with slightly distorted voltage due to random harmonics
Author
Raonic, D. ; Cyganski, David ; Emanuel, Alexander E.
Author_Institution
Dept. of Electr. Eng., Titograd Univ., Yugoslavia
Volume
4
Issue
1
fYear
1989
fDate
1/1/1989 12:00:00 AM
Firstpage
502
Lastpage
507
Abstract
The effect of random current and voltage harmonics combined with random loads on the value of the optimum capacitor for power factor correction is analyzed. Special attention is given to the standard deviation of the energy loss in the feeder. It is proved that static VAr compensators are one of the most effective means for reduction of the energy losses in transmission and distribution lines
Keywords
power factor correction; power systems; static VAr compensators; power factor compensation; power systems; static VAr compensators; voltage distortion; Energy loss; Equivalent circuits; Harmonic analysis; Harmonic distortion; Impedance; Power capacitors; Power system harmonics; Reactive power; Rectifiers; Voltage;