DocumentCode :
846786
Title :
Protecting NYSEG´s six-phase transmission line
Author :
Apostolov, Alexander ; George, William
Author_Institution :
New York State Electric & Gas Corp., NY, USA
Volume :
5
Issue :
4
fYear :
1992
Firstpage :
33
Lastpage :
36
Abstract :
The high phase order transmission demonstration project is described. An existing 115 kV double-circuit transmission line was electrically reconfigured into a single-circuit, six-phase transmission line for this purpose. A description is given for different computer applications used in all stages of design, operation, and postoperation analysis. The complex multirelay microprocessor-based protection system is discussed. The multirelay microprocessor protection system was tested for many typical fault combinations using a computer controlled fault simulator. Currents and voltages were calculated using the Electromagnetic Transient Program (EMTP).<>
Keywords :
electrical faults; microcomputer applications; power engineering computing; power transmission lines; relay protection; 6-phase transmission lines; 93 kV; Electromagnetic Transient Program; New York State Electric and Gas Corporation; computer controlled fault simulator; currents; fault combinations; multirelay microprocessor-based protection system; voltages; Circuit faults; Computational modeling; Computer applications; Digital relays; Distributed parameter circuits; Power system protection; Power transmission lines; Protective relaying; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Computer Applications in Power, IEEE
Publisher :
ieee
ISSN :
0895-0156
Type :
jour
DOI :
10.1109/67.160044
Filename :
160044