DocumentCode :
847412
Title :
Report on enclosure internal arcing tests
Author :
Heberlein, G. Erich, Jr. ; Higgins, Jack A. ; Epperly, Richard A.
Author_Institution :
Allen-Bradley Co., Milwaukee, WI, USA
Volume :
2
Issue :
3
fYear :
1996
Firstpage :
35
Lastpage :
42
Abstract :
The improvement of electrical equipment is an ongoing process including investigative research. This is a report on research work concerning factors regarding high-energy arcing faults, the tests conducted on containment of these faults, and standards addressing arcing fault test requirements. This report is focused on low-voltage, 600 V class motor control centers (MCCs), but the issues presented should not be limited to only this type of electrical equipment. Also, the scope of this work is restricted to a high-energy arcing fault occurring in a latched or closed compartment during “normal” operating conditions and does not include arcing faults occurring in compartments when the compartment door is open
Keywords :
arcs (electric); electric motors; electrical faults; machine control; testing; 600 V; arcing faults containment; closed compartment; electrical equipment; enclosure internal arcing tests; high-energy arcing faults; motor control centers; normal operating conditions; Chemical industry; Explosions; IEEE members; Injuries; Motor drives; Petroleum; Protection; Protective clothing; Switches; Testing;