    Impact of stray capacitance on HVDC harmonics

  • Author

    Larsen, E.V. ; Sublich, M. ; Kapoor, S.C.

  • Author_Institution
    General Electric Co., Schenectady, NY, USA
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    1/1/1989 12:00:00 AM
  • Firstpage
    637
  • Lastpage
    645
  • Abstract
    Stray capacitances inherent to HVDC converters are shown to cause all triplen harmonics to appear on the DC side. In particular, odd-triplen harmonics are produced which in a bipolar DC system will cause ground-mode simulation of the DC transmission line. The levels predicted by simulation can be large enough to cause significant telephone interference if the DC filtering, including both pole and neutral buses, is not designed to accommodate these harmonics. Field experience provides qualitative support for this theory
  • Keywords
    DC transmission networks; power convertors; DC transmission line; HVDC converters; ground-mode simulation; odd-triplen harmonics; stray capacitance; Capacitance; Frequency conversion; HVDC transmission; Inductors; Insulators; Interference; Power harmonic filters; Smoothing methods; Telephony; Valves;