Impact of stray capacitance on HVDC harmonics
Author :
Larsen, E.V. ; Sublich, M. ; Kapoor, S.C.
Author_Institution :
General Electric Co., Schenectady, NY, USA
Volume :
4
Issue :
1
fYear :
1989
fDate :
1/1/1989 12:00:00 AM
Firstpage :
637
Lastpage :
645
Abstract :
Stray capacitances inherent to HVDC converters are shown to cause all triplen harmonics to appear on the DC side. In particular, odd-triplen harmonics are produced which in a bipolar DC system will cause ground-mode simulation of the DC transmission line. The levels predicted by simulation can be large enough to cause significant telephone interference if the DC filtering, including both pole and neutral buses, is not designed to accommodate these harmonics. Field experience provides qualitative support for this theory
Keywords :
DC transmission networks; power convertors; DC transmission line; HVDC converters; ground-mode simulation; odd-triplen harmonics; stray capacitance; Capacitance; Frequency conversion; HVDC transmission; Inductors; Insulators; Interference; Power harmonic filters; Smoothing methods; Telephony; Valves;
fLanguage :
English