• DocumentCode
    847528
  • Title

    Dynamic measurements during short-circuit testing of transformers part II: Test results and analysis

  • Author

    Ayers, R.E. ; Usry, G.O. ; Patel, M.R. ; Steel, R.B.

  • Author_Institution
    General Electric Company, Rome, Georgia
  • Volume
    94
  • Issue
    2
  • fYear
    1975
  • fDate
    3/1/1975 12:00:00 AM
  • Firstpage
    198
  • Lastpage
    206
  • Abstract
    Some of the test results measured during short circuit tests on a full size, 19.5 MVA, three phase, three winding, oil filled, power transformer are reported and analyzed in this paper. Included are radial flux measurements to obtain accurate calculated electromagnetic forces, the effects of tap configuration and clamping force on the dynamic forces transmitted to various parts of the transformer structure, comparison of the measured results with computer predicted results, the circumferential force variation at the top of the winding, the forces experienced by the tie plates, and the failure detection results.
  • Keywords
    Circuit testing; Clamps; Electromagnetic forces; Electromagnetic measurements; Force measurement; Petroleum; Phase measurement; Power measurement; Power transformers; Size measurement;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1975.31842
  • Filename
    1601444