• DocumentCode
    847536
  • Title

    An investigation of the horizontally mounted insulators for HVDC stations

  • Author

    Naito, Katsuhiko ; Matsuoka, Ryosuke ; Ito, Susumu ; Morikawa, Satoshi

  • Author_Institution
    NGK Insulators Ltd., Nagoya, Japan
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    1/1/1989 12:00:00 AM
  • Firstpage
    653
  • Lastpage
    666
  • Abstract
    The results of investigations into the cause of certain flashovers which occurred in horizontally mounted insulators in HVDC stations are described. Insulators having various shed shapes were subjected to contamination and wet tests under horizontally and vertically mounted insulators, a slight reduction was found in the contamination withstand voltages of horizontally mounted insulators for some shed profiles. A shed shape is proposed as the optimum design for horizontally mounted insulators from the viewpoint of both contamination and wet withstand voltage
  • Keywords
    flashover; insulators; substations; testing; HVDC stations; contamination tests; horizontally mounted insulators; shed profiles; wet tests; Coatings; Flashover; HVDC transmission; Insulation; Insulator testing; Rain; Rubber; Shape; Surface contamination; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.19258
  • Filename
    19258