An investigation of the horizontally mounted insulators for HVDC stations
Author
Naito, Katsuhiko ; Matsuoka, Ryosuke ; Ito, Susumu ; Morikawa, Satoshi
Author_Institution
NGK Insulators Ltd., Nagoya, Japan
Volume
4
Issue
1
fYear
1989
fDate
1/1/1989 12:00:00 AM
Firstpage
653
Lastpage
666
Abstract
The results of investigations into the cause of certain flashovers which occurred in horizontally mounted insulators in HVDC stations are described. Insulators having various shed shapes were subjected to contamination and wet tests under horizontally and vertically mounted insulators, a slight reduction was found in the contamination withstand voltages of horizontally mounted insulators for some shed profiles. A shed shape is proposed as the optimum design for horizontally mounted insulators from the viewpoint of both contamination and wet withstand voltage
Keywords
flashover; insulators; substations; testing; HVDC stations; contamination tests; horizontally mounted insulators; shed profiles; wet tests; Coatings; Flashover; HVDC transmission; Insulation; Insulator testing; Rain; Rubber; Shape; Surface contamination; Voltage;