• DocumentCode
    847563
  • Title

    Effects of grounding on distribution system harmonic resonance conditions

  • Author

    MelioPoulos, A. P Sakis ; Cokkinides, G.J. ; Chakravarthi, K.R.

  • Author_Institution
    Georgia Inst. of Technol., Atlanta, GA, USA
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    1/1/1989 12:00:00 AM
  • Firstpage
    675
  • Lastpage
    682
  • Abstract
    An analytic model is presented which predicts the impact of soil resistivity, grounding, and electric load on power system resonance characteristics. A parametric study is reported which illustrates the significance of these parameters and provides a quantitative evaluation of their effects. The predictions of the model are compared with experimental data obtained from an actual 12 kV power distribution system
  • Keywords
    distribution networks; earthing; harmonics; power system analysis computing; transmission network calculations; 12 kV; analytic model; computer model; distribution system; electric load; grounding; harmonic resonance conditions; parametric study; power system resonance characteristics; soil resistivity; Conductivity; Grounding; Parametric study; Power distribution; Power system analysis computing; Power system harmonics; Power system modeling; Predictive models; Resonance; Soil;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.19260
  • Filename