DocumentCode :
847563
Title :
Effects of grounding on distribution system harmonic resonance conditions
Author :
MelioPoulos, A. P Sakis ; Cokkinides, G.J. ; Chakravarthi, K.R.
Author_Institution :
Georgia Inst. of Technol., Atlanta, GA, USA
Volume :
4
Issue :
1
fYear :
1989
fDate :
1/1/1989 12:00:00 AM
Firstpage :
675
Lastpage :
682
Abstract :
An analytic model is presented which predicts the impact of soil resistivity, grounding, and electric load on power system resonance characteristics. A parametric study is reported which illustrates the significance of these parameters and provides a quantitative evaluation of their effects. The predictions of the model are compared with experimental data obtained from an actual 12 kV power distribution system
Keywords :
distribution networks; earthing; harmonics; power system analysis computing; transmission network calculations; 12 kV; analytic model; computer model; distribution system; electric load; grounding; harmonic resonance conditions; parametric study; power system resonance characteristics; soil resistivity; Conductivity; Grounding; Parametric study; Power distribution; Power system analysis computing; Power system harmonics; Power system modeling; Predictive models; Resonance; Soil;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.19260
Filename :
19260
Link To Document :
بازگشت