DocumentCode :
847805
Title :
Prediction of surge response of a symmetrically excited three-phase line,and comparison with experimental results
Author :
Magnusson, P.C.
Volume :
94
Issue :
2
fYear :
1975
fDate :
3/1/1975 12:00:00 AM
Firstpage :
416
Lastpage :
424
Abstract :
The traveling-wave response of a 33-kV, flat-spaced three-phase line to symmetrically impressed double-exponential-surge excitation was predicted from Carson´s equations. The following modified asymptotic approximation was derived for the propagation functions of the two symmetrical-type natural modes. rAn= s√µ0ε0+ b1√s+η+b2Here η = 2(b2b1)2if b2< 0 (high-loss mode); η = 0 if b2> 0 (low-loss mode). The approximate voltage transform in terms of γAnhas a closed-form inverse. Numerical integration was used to compute a corrective voltage term. Predicted results for distances from 0.8 miles to 7.98 miles from the source compared favorably with earlier oscillograms for voltages below the corona-onset level.
Keywords :
Conductivity; Conductors; Earth; Equations; Frequency; Physics computing; Surges; Testing; Transmission line matrix methods; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1975.31868
Filename :
1601470
Link To Document :