Prediction of surge response of a symmetrically excited three-phase line,and comparison with experimental results
Author
Magnusson, P.C.
Volume
94
Issue
2
fYear
1975
fDate
3/1/1975 12:00:00 AM
Firstpage
416
Lastpage
424
Abstract
The traveling-wave response of a 33-kV, flat-spaced three-phase line to symmetrically impressed double-exponential-surge excitation was predicted from Carson´s equations. The following modified asymptotic approximation was derived for the propagation functions of the two symmetrical-type natural modes. rAn = s√µ0 ε0 + b1 √s+η+b2 Here η = 2(b2 b1 )2if b2 < 0 (high-loss mode); η = 0 if b2 > 0 (low-loss mode). The approximate voltage transform in terms of γAn has a closed-form inverse. Numerical integration was used to compute a corrective voltage term. Predicted results for distances from 0.8 miles to 7.98 miles from the source compared favorably with earlier oscillograms for voltages below the corona-onset level.
Keywords
Conductivity; Conductors; Earth; Equations; Frequency; Physics computing; Surges; Testing; Transmission line matrix methods; Voltage;