DocumentCode :
847814
Title :
Behavior of the hydro-quebec 735-kV system under transient short-circuit conditions and its digital computer simulation
Author :
Malewski, Ryszard ; Narancic, Vojislav N. ; Robichaud, Yvan
Author_Institution :
Hydro-Quebec Institute of Research, Varennes, Quebec, Canada
Volume :
94
Issue :
2
fYear :
1975
fDate :
3/1/1975 12:00:00 AM
Firstpage :
425
Lastpage :
431
Abstract :
Five single-phase short-circuit tests were performed on the live 735-kV system. Transient currents and voltages were recorded on magnetic tape. The transmission system under fault conditions was simulated on a digital computer. The measured and simulated transients were superimposed on the same graphs using a computer-controlled plotter. The accuracy of measurements was evaluated and the graphs of the simulated transients were compared with those of the measured ones. This comparative study was then used for an experimental check of the computer simulation and provided reassurance that the system modeling was precise enough for further transient analyses.
Keywords :
Area measurement; Computational modeling; Computer simulation; Power system transients; Resistors; Substations; System testing; Transient analysis; Transmission line measurements; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1975.31869
Filename :
1601471
Link To Document :
بازگشت