Title
Measurement of switching transients in 115 kV substation
Author
Wiggins, C.M. ; Nickel, F.S. ; Haney, A.J. ; Wright, S.E.
Author_Institution
BDM Corp., Albuquerque, NM, USA
Volume
4
Issue
1
fYear
1989
fDate
1/1/1989 12:00:00 AM
Firstpage
756
Lastpage
769
Abstract
Bus current transients, electric and magnetic field transients, and current transients coupled onto control and CT cables produced by switching operations in a 115 kV ring bus have been measured and characterized. The similarities and differences among transients observed when energizing and deenergizing relatively short sections of bus during disconnect switch and circuit breaker opening and closing operations are summarized and discussed. The results are used to further the understanding of switching transient characteristics and to validate a model that predicts the detailed nature of the transients reported, for use in ongoing investigations to assure continued satisfactory performance in substation protection equipment
Keywords
switching substations; transients; 115 kV; bus current transients; circuit breaker; disconnect switch; electric field transients; magnetic field transients; ring bus; substation; switching transients; Cables; Circuit breakers; Coupling circuits; Current measurement; Electric variables measurement; Magnetic field measurement; Magnetic switching; Substations; Switches; Switching circuits;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.19268