• DocumentCode
    848163
  • Title

    Current and voltage harmonic measurements and modeling at the Gardner photovoltaic project

  • Author

    Cyganski, D. ; Orr, J.A. ; Chakravorti, A.K. ; Emanuel, A.E. ; Gulachenski, E.M. ; Root, C.E. ; Bellemare, R.C.

  • Author_Institution
    Worcester Polytech. Inst., MA, USA
  • Volume
    4
  • Issue
    1
  • fYear
    1989
  • fDate
    1/1/1989 12:00:00 AM
  • Firstpage
    800
  • Lastpage
    809
  • Abstract
    Measurements on harmonics taken at the Gardner photovoltaic (PV) project during the summer of 1987 are reported. The project includes 28 PV homes, each with a roof-mounted 2 kW PV system, connected to one phase of a 13.8 kV three-phase feeder. The measurements discussed pertain to voltage and current distortion and power flow. Theoretical calculations were carried out in order to study the effects of PV inverters other than the type installed for this study. Computer modeling of the feeder in Gardner indicates, and measurements confirm, that small increases (0.2%) in voltage total harmonic distortion will occur on this feeder with the indicated penetration of PV systems using high-quality, forced-commutation inverters
  • Keywords
    harmonics; photovoltaic power systems; 13.8 kV; 2 kW; Gardner photovoltaic project; PV inverters; current distortion; current harmonics; forced-commutation inverters; harmonics measurement; power flow; three-phase feeder; voltage distortion; voltage harmonics; Current measurement; Distortion measurement; Fluid flow measurement; Inverters; Load flow; Photovoltaic systems; Power measurement; Power system modeling; Solar power generation; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.19273
  • Filename
    19273