DocumentCode :
848330
Title :
The operation of a parametric transformer between two busbars
Author :
Fam, W.Z. ; Sen, P.K.
Author_Institution :
Nova Scotia Technical College, Halifax, Nova Scotia, Canada
Volume :
94
Issue :
3
fYear :
1975
fDate :
5/1/1975 12:00:00 AM
Firstpage :
858
Lastpage :
865
Abstract :
This paper deals with the operation of a parametric transformer when both the input and output windings are connected to live busbars. The relationship between each core flux and the MMF\´s of the two windings is explained. Based on this relationship, the voltage equations of the device are integrated numerically to obtain the input and output currents and the power-angle characteristics. The effects of the phase angle "δ" between the two busbar voltages on the power flow, efficiency, power factor and harmonic currents are examined. A comparison between the experimental results on a small unit and those obtained from the numerical solution of the equations is also given.
Keywords :
Coils; Educational institutions; Equations; Inductance; Load flow; Magnetic circuits; Magnetic cores; Oscillators; Power systems; Transformer cores;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1975.31916