Title :
A half cycle static bus protection relay using instantaneous voltage measurement
Author_Institution :
General Electric Co., Philadelphia, Pa.
fDate :
5/1/1975 12:00:00 AM
Abstract :
A high impedance bus protection relay using thyristors and based on instantaneous voltage measurement is described. Half-cycle operating speed is achieved and power dissipation is minimized. Application is no longer limited by the kneepoint of the C.T. excitation characteristic and peak C.T. secondary voltages are accurately limited, regardless of fault magnitude.
Keywords :
Circuit faults; Equations; Fault currents; Protection; Protective relaying; Relays; Resistors; Solid state circuits; Switches; Voltage measurement;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :