DocumentCode
848953
Title
Overvoltage phenomena associated with virtual current chopping in three phase circuits
Author
Panek, J. ; Fehrle, K.G.
Author_Institution
General Electric Company, Philadelphia, Pennsylvania
Volume
94
Issue
4
fYear
1975
fDate
7/1/1975 12:00:00 AM
Firstpage
1317
Lastpage
1325
Abstract
Switching of three phase load currents with low power factors, such as encountered in arc furnace installations can result in a series of reignitions and clearings. Depending on the switch performance and system parameters the switching transients may involve one, two, or three phases. The effect of virtual current chopping which can lead to line to line overvoltages is described. The phenomena are explained for simplified conditions, more complex situations are handled by digital computer studies.
Keywords
Breakdown voltage; Capacitance; Circuits; Furnaces; Manufacturing processes; Power capacitors; Power transformer insulation; Reactive power; Switches; Voltage control;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.31969
Filename
1601571
Link To Document