Preliminary qualification of a HPOF pipe cable system for service at 765 kv
Author :
Engelhardt, J.S. ; Blodgett, R.B.
Author_Institution :
The Anaconda Company, Greenwich, Connecticut
Volume :
94
Issue :
5
fYear :
1975
Firstpage :
1569
Lastpage :
1583
Abstract :
Tan δ (dissipation factor)data on Cable System B is updated to include the full 2-year 500/550 kV test program at Waltz Mill and the 10-month 765/800 kV extended test program. This data is analyzed, demonstrating no change with time of tan δ for the system. Particular attention is paid to the paper splice, which exhibits a thermoelectric stability limitation at the 765/800 kV level. The outstanding performance of the PP/C splice is emphasized. Consideration of the operation of a very highly stressed oil impregnated paper insulation HPOF pipe system at 765 kV is suggested, including potential single circuit transmission capacity calculations.
Keywords :
Automatic testing; Communication cables; Conductors; Cooling; Oil insulation; Petroleum; Qualifications; System testing; Temperature; Voltage;