• DocumentCode
    849404
  • Title

    Ground fault protection for electric utility generating station 480-volt auxiliary power systems

  • Author

    Love, Daniel J.

  • Author_Institution
    Bechtel Power Corporation, Los Angeles, California
  • Volume
    94
  • Issue
    5
  • fYear
    1975
  • Firstpage
    1689
  • Lastpage
    1697
  • Abstract
    Many generating station 480-volt auxiliary power systems employ a WYE distribution system with the source neutral solidly grounded. Because of the arcing nature of some ground faults, the ground fault currents developed on these systems are often too low to operate phase overcurrent protective devices. As WYE systems became more popular, a more sophisticated approach to protection was needed, resulting in the development of many new protective devices for ground fault protection. This paper reviews the application of such ground fault protective devices for use in 480-volt auxiliary power systems of generating stations. In addition, some modifications to existing products are suggested.
  • Keywords
    Circuit faults; Electric breakdown; Fault currents; Fault detection; Grounding; Power generation; Power system faults; Power system protection; Power system reliability; Power transformer insulation;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1975.32012
  • Filename
    1601614