DocumentCode :
849703
Title :
A field study of the short-line-fault component of transient recovery voltage
Author :
Colclaser, R.C., Jr. ; Beehler, J.E. ; Garrity, T.F.
Author_Institution :
University of Pittsburgh, Pittsburgh, Pa
Volume :
94
Issue :
6
fYear :
1975
Firstpage :
1943
Lastpage :
1953
Abstract :
The short-line-fault transient recovery voltage component is a critical factor in arc interruption. This paper is a study of 345kV field data, generated by a pulse test circuit, which develops inherent characteristics for the "bare" line. The modifying effects of terminal equipment on the shape of the saw-tooth component are demonstrated experimentally and theoretically. Test results are compared with present ANSI Standard requirements to verify the application.
Keywords :
Current measurement; Diodes; Inductors; Interrupters; Oscilloscopes; Poles and towers; Pulse transformers; Test equipment; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1975.32040
Filename :
1601642
Link To Document :