DocumentCode
849749
Title
General expression for positive switching impulse strength valid up to extra long air gaps
Author
Gallet, G. ; Leroy, G. ; Lacey, R. ; Kromer, I.
Author_Institution
Electricite de France, Paris
Volume
94
Issue
6
fYear
1975
Firstpage
1989
Lastpage
1993
Abstract
A new algebraic expression has been established for the critical sparkover voltage (CSOV) afair insulation submitted to positive switching impulses. By using the concept of the gap factor, the expression is found to be valid for all practical gap configurations in the distance range 1 to at least 30 m. Based on these considerations, an absolute limit of 2.4 MV is foreseen for the rated voltage of AC systems. Sparkover voltages under A.C. or lightning impulses are also predictable. Complementary investigations concerning the physics of discharge are needed for further improvements.
Keywords
Air gaps; Circuit testing; Genetic expression; Geometry; Laboratories; Linearity; Physics; Senior members; Shape; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.32045
Filename
1601647