DocumentCode
849865
Title
Measurement of short circuit load losses in large three phase power transformers using an alternating current comparator bridge
Author
Moore, W.J.M. ; Love, G. ; Raftis, F.A.
Author_Institution
National Research Council of Canada, Ottawa
Volume
94
Issue
6
fYear
1975
Firstpage
2074
Lastpage
2076
Abstract
The application of a high-voltage alternating-current-comparator capacitance bridge to the measurement of the short circuit load losses of large three phase power transformers at rated current is described. Input of the transformer current to the bridge is provided through a 1000/1 ratio two-stage current transformer with a single turn primary winding Insulated for 50 kilovolts. Voltage input is provided through a loss-free gas dielectric capacitor which serves as the reference. Measurements on typical transformers ranging in size from 450 MVA to 750 MVA; with currents from 600 to 2100 amperes and short-clrcuit power factors from one percent to four percent, are discussed. Comparisons to appropriately corrected wattmeter measurements (aided by low-loss capacitors connected in parallel with the transformer) indicate an overall agreement of better than one percent.
Keywords
Bridge circuits; Capacitors; Current measurement; Current transformers; Dielectric losses; Loss measurement; Phase measurement; Power measurement; Power transformer insulation; Power transformers;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1975.32056
Filename
1601658