DocumentCode :
850087
Title :
Performance testing of a long distance radial static VAr compensated transmission system and validation of simulation results
Author :
Choi, S.S. ; Stewart, J.R. ; Singh, B. ; Carrington, P.F. ; Goddard, E.H. ; Carter, C.E.
Author_Institution :
State Energy Comm. of Western Australia, Perth, WA, Australia
Volume :
3
Issue :
4
fYear :
1988
fDate :
11/1/1988 12:00:00 AM
Firstpage :
1509
Lastpage :
1517
Abstract :
The authors present selected results of recent field tests carried out on the 220 kV, 660 km radial static VAr (volt-ampere reactive) compensated Muja-Kalgoorlie transmission system in Western Australia. Measured results on network harmonics, SVC (static VAr compensator) losses and the responses of the power system under small and large-disturbance conditions are discussed. The recorded data have also been used to validate and improve the computer models used in simulation studies
Keywords :
digital simulation; power engineering computing; power systems; static VAr compensators; 220 kV; 660 km; Muja-Kalgoorlie transmission system; SVC losses; Western Australia; computer models; field tests; long distance radial static VAr compensated transmission system; network harmonics; performance testing; simulation results; Australia; Loss measurement; Power measurement; Power system harmonics; Power system measurements; Power system modeling; Power system simulation; Reactive power; Static VAr compensators; System testing;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.192960
Filename :
192960
Link To Document :
بازگشت