• DocumentCode
    850295
  • Title

    Power circuit breaker transient recovery voltages

  • Author

    Hedman, D.E. ; Lambert, S.R.

  • Author_Institution
    Power Technologies, Inc., Schenectady, N.Y.
  • Volume
    95
  • Issue
    1
  • fYear
    1976
  • Firstpage
    197
  • Lastpage
    207
  • Abstract
    This paper describes the effects of the system zero-sequence network impedances and bus capacitance on circuit breaker transient recovery voltage requirements for EHV systems. Three basic types of faults are considered: three-phase-to-ground terminal faults, three-phase ungrounded terminal faults, and short line faults. Comparisons are presented between conventional methods of calculation used in the ANSI and IEC Standards and a more exact method which considers a simulation of the zero-sequence impedance of the system, including frequency dependence of the line surge impedances. The sensitivity of transient recovery voltages to bus capacitance is also shown for both source and line-side capacitances. The effect of bundled subconductors clashing at high fault levels is also shown and an approximate method of predicting the clashed configuration is presented. Comments on circuit breaker testing are included.
  • Keywords
    Capacitance; Circuit breakers; Circuit faults; Circuit simulation; Circuit testing; Frequency dependence; IEC standards; Impedance; Surges; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1976.32092
  • Filename
    1601694