Field measurements and calculations of electrostatic effects of overhead transmission lines
Author
Bracken, T.D.
Author_Institution
Bonneville Power Administration, Portland, Oregon
Volume
95
Issue
2
fYear
1976
fDate
3/1/1976 12:00:00 AM
Firstpage
494
Lastpage
504
Abstract
The results of an electrostatic measurements program held in conjunction with the IEEE Working Group on E/S and E/M Effects of Transmission Lines and attended by representatives of several organizations are presented. Measurements were made at ground level under an energized 525-kV line of electric field intensity, of induced currents and voltages on objects, and of perception and annoyance levels of men, women, and children for steady state and transient shocks. Three types of field strength meter were employed. They gave consistent readings in agreement with predicted field strength. Analytical estimates of short circuit current for various objects are in agreement with measured values.
Keywords
Current measurement; Electric shock; Electric variables measurement; Electrostatic measurements; Energy measurement; Power system transients; Power transmission lines; Steady-state; Transmission line measurements; Voltage;