DocumentCode
850852
Title
The effects of non-transposition and earth return frequency dependence on transients due to high speed reclosing
Author
Kassakian, John G.
Author_Institution
Massachusetts Institute of Technology, Cambridge, Massachusetts
Volume
95
Issue
2
fYear
1976
fDate
3/1/1976 12:00:00 AM
Firstpage
610
Lastpage
620
Abstract
The effects of modeling non-transposition and the frequency dependence of the earth return on switching surges caused by high speed reclosing operations are studied. Theoretical and experimental results are in close agreement. Comparisons are based on the probability density distribution of overvoltages and the consequences of the different modeling techniques are illustrated with a simple line design example.
Keywords
Earth; Frequency dependence; Impedance; Power engineering and energy; Power system modeling; Power system transients; Power transmission lines; Surges; Systems engineering and theory; Transmission line theory;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/T-PAS.1976.32142