• DocumentCode
    851468
  • Title

    Audible noise performance of the first three-phase ultra-high voltage transmission test line at EPRI´s project UHV

  • Author

    Comber, M.G. ; Nigbor, Richard J.

  • Author_Institution
    General Electric Company, Pittsfield, Massachusetts
  • Volume
    95
  • Issue
    4
  • fYear
    1976
  • fDate
    7/1/1976 12:00:00 AM
  • Firstpage
    1105
  • Lastpage
    1114
  • Abstract
    A three-phase ultra-high voltage transmission test line at EPRI´s Project UHV was energized in January 1975. Analyses of the audible noise performance of the first six-months of energization are presented. The result of long-term energization during foul-weather are reported in terms of cumulative frequency distributions, lateral profiles and frequency spectra. Audible noise variations with voltage in rain and fair weather are also presented. Results are compared with calculations made on the basis of single-phase tests. Good agreement between measured and calculated performances is demonstrated.
  • Keywords
    Acoustic noise; Books; Conductors; Corona; Frequency; Phase measurement; Power transmission lines; Testing; Transmission line measurements; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1976.32203
  • Filename