DocumentCode :
852003
Title :
Frequency of distribution arrester discharge currents due to direct strokes
Author :
Brown, Gordon W. ; Thunander, Steven
Author_Institution :
Joslyn Mfg. Co., Chicago, Illinois
Volume :
95
Issue :
5
fYear :
1976
Firstpage :
1571
Lastpage :
1578
Abstract :
The "Electrogeometric" Theory, developed for transmission line lightning performance calculations, is applied to distribution systems as a means of predicting arrester discharge currents. The resulting rates of occurrence and frequency distributions compare favorably with presently available information. The effect of stroke location on attester current is explained and shown to be significant. Predischarge and pole reflections are shown to have similar effects, and do not significantly affect crest current. Footing resistance is accounted for. Indirect strokes are treated briefly and shown to produce minimal arrester current.
Keywords :
Arresters; Conductors; Earth; Equations; Frequency; Meetings; Power & Energy Society; Printing; Surges; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1976.32256
Filename :
1601858
Link To Document :
بازگشت