Title :
Harmonics caused by imbalanced transformer impedances and imperfect twelve-pulse operation in HVDC conversion
Author :
Subbarao, T. ; Reeve, J.
Author_Institution :
General Electric Company, Philadelphia, USA
Abstract :
In substituting a degree of imbalance between the phase impedances of HVdc converter transformers for the usual assumption of equal impedances, the generated ac harmonics are modified and triplen (non-characteristic) harmonics are produced. They are analysed and assessed; and are not expected to be serious provided due attention is paid to impedance balancing. Certain normal harmonics for 6-pulse operation are ideally eliminated by 12-pulse operation. An analysis is made of the extent of residual 6-pulse harmonics due to the imperfect balance of 12-pulse bridge operation. The paper provides a basis for specifying certain design tolerances.
Keywords :
Bridge circuits; Equations; HVDC transmission; Impedance; Meetings; Power & Energy Society; Power engineering computing; Power harmonic filters; Resonance; Valves;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/T-PAS.1976.32272