• DocumentCode
    852248
  • Title

    Particularities of air insulation behavior

  • Author

    Menemenlis, C. ; Harbec, G.

  • Author_Institution
    Hydro-Quebec Institute of Research, Varennes, Quebec, Canada
  • Volume
    95
  • Issue
    6
  • fYear
    1976
  • Firstpage
    1814
  • Lastpage
    1821
  • Abstract
    In actual practice the withstand voltage level of air insulation is estimated by an extrapolation based on the 50% breakdown voltage, U50%, and the standard deviation, σ both obtained by laboratory tests. For this extrapolation to be possible it is assumed that the breakdown probability follows a gaussian distribution. It is observed however that in many cases this distribution deviates appreciably from a normal. Unexpected inconsistencies of the breakdown probability are also observed. This particular behavior of air insulation is studied in the present report and a physical explanation is attempted.
  • Keywords
    Breakdown voltage; Electric breakdown; Extrapolation; Humidity; Insulation testing; Laboratories; Performance evaluation; Probability; Temperature; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1976.32282
  • Filename
    1601884