Particularities of air insulation behavior
Author :
Menemenlis, C. ; Harbec, G.
Author_Institution :
Hydro-Quebec Institute of Research, Varennes, Quebec, Canada
Volume :
95
Issue :
6
fYear :
1976
Firstpage :
1814
Lastpage :
1821
Abstract :
In actual practice the withstand voltage level of air insulation is estimated by an extrapolation based on the 50% breakdown voltage, U50%, and the standard deviation, σ both obtained by laboratory tests. For this extrapolation to be possible it is assumed that the breakdown probability follows a gaussian distribution. It is observed however that in many cases this distribution deviates appreciably from a normal. Unexpected inconsistencies of the breakdown probability are also observed. This particular behavior of air insulation is studied in the present report and a physical explanation is attempted.
Keywords :
Breakdown voltage; Electric breakdown; Extrapolation; Humidity; Insulation testing; Laboratories; Performance evaluation; Probability; Temperature; Voltage control;