• DocumentCode
    852343
  • Title

    Compressed air, the solution for generator breakers problems

  • Author

    Thuries, E. ; Mallez, B. ; Van Doan, Pham ; Jeanjean, R.

  • Author_Institution
    Delle-Alsthom, Villeurbanne, France
  • Volume
    95
  • Issue
    6
  • fYear
    1976
  • Firstpage
    1901
  • Lastpage
    1910
  • Abstract
    A high arc voltage being essential to interrupt currents without a zero pause, it has become compulsory to use compressed air as an interrupting medium in generator breakers. The use of compressed air for cooling purposes has resulted in simpler, hence more reliable breakers. The circuit breakers PKG have been subjected to short-circuit current interruptions up to 340 kA. For configurations where the generator delivers through two transformers, a new arrangement of interrupting equipment has been proposed in order to meet the resulting increase of short-circuit currents.
  • Keywords
    Circuit breakers; Cooling; Dielectrics; Flammability; Manufacturing; Petroleum; Power generation; Switches; Transformers; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1976.32291
  • Filename
    1601893