Abstract :
The application of a diode bridge rectifier unit connected to a generator feeding a sending-end HVDC station shows a substantial reduction in the station cost. One of the major problems of this configuration is its slow recovery from a DC line fault. The authors propose and analyze a few types of control and protection schemes for the generator. The minimum time required to restore full power subsequent to a DC line fault is studied for each scheme. The results of a digital computer study are presented, as are some results obtained from a real-time physical component HVDC simulator
Keywords :
DC power transmission; diodes; electric generators; failure analysis; power engineering computing; rectifiers; DC line fault; diode valve rectifier scheme; electric generators; protection schemes; sending-end HVDC station; Bridges; Computational modeling; Computer simulation; Costs; Diodes; HVDC transmission; Physics computing; Protection; Rectifiers; Valves;
Journal_Title :