DocumentCode :
852544
Title :
Apparent impedance measuring systems (AIMS)
Author :
Agrawal, B.L. ; Demcko, J.A. ; Farmer, R.G. ; Selin, D.A.
Author_Institution :
Arizona Public Service Co., Phoenix, AZ, USA
Volume :
4
Issue :
2
fYear :
1989
fDate :
5/1/1989 12:00:00 AM
Firstpage :
575
Lastpage :
585
Abstract :
For the analysis of subsynchronous resonance, computer models of an electric system have generally been based on a modified 60 Hz model with short-circuit equivalents for power sources and with loads neglected. Due to the importance of validating the electric systems model, AIMS has been developed to measure the apparent impedance as a function of frequency seen at the terminals of the study generator. AIMS has been successfully applied to an extensive power system. A description is given of AIMS and the significant modeling improvement realized by it application
Keywords :
electric impedance measurement; power system analysis computing; power system measurement; 60 Hz; AIMS; apparent impedance measuring system; frequency; generator; modeling; power sources; power system analysis computing; subsynchronous resonance; Artificial intelligence; Current measurement; Electric variables measurement; Frequency; Impedance measurement; Low pass filters; Phase measurement; Time measurement; Voltage; Wideband;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.193832
Filename :
193832
Link To Document :
بازگشت