• DocumentCode
    852930
  • Title

    Electromagnetic forces in a plane six-bus system

  • Author

    Koch, Bohdan

  • Author_Institution
    Inst. de Recherche d´´Hydro, Varennes, Que., Canada
  • Volume
    3
  • Issue
    3
  • fYear
    1988
  • fDate
    7/1/1988 12:00:00 AM
  • Firstpage
    947
  • Lastpage
    953
  • Abstract
    In some electric substations, such as those comprising series-compensation equipment, the shunt buswork forms a plane three-phase system of six parallel buses. This system is exposed to the electrodynamic effects of both symmetrical and asymmetrical faults that results in current flow in two to all six of the buses concerned. The studies reported show that the maximum forces in such a system usually exceed the values expected in a plane three-phase system comprising three buses
  • Keywords
    busbars; electrical faults; electrodynamics; electromagnetic fields; substations; EM forces; asymmetrical faults; electric substations; electrodynamic effects; plane six-bus system; series-compensation equipment; shunt buswork; symmetrical faults; three-phase system; Circuit faults; Conductors; Electrodynamics; Electromagnetic forces; Fault diagnosis; Impedance; Power & Energy Society; Printing; Shunt (electrical); Substations;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.193872
  • Filename