Abstract :
The authors provide an indication of the waveshape and magnitude of transients which emerge from the SF6 GIS and propagate to externally connected apparatus. Capacitively graded bushings, overhead line connections, etc. tend to reduce the magnitude and cause a slight degradation in the rise-time. Computer simulations and measurements have shown that external apparatus connected to GIS can be subjected to waveforms with rise-times in the range of 10-20 ns and voltage rate-of-rise as high as 40 MV/μs. This is comparable to or in excess of the rate of rise during a chopped wave test
Keywords :
digital simulation; gaseous insulation; substations; sulphur compounds; transients; 10 to 20 ns; SF6; capacitively graded bushings; computer simulations; disconnector-induced short rise-time transients; externally connected power system components; gas insulated substations; overhead line connections; waveshape; Computational Intelligence Society; Degradation; Frequency; Geographic Information Systems; Impedance; Insulators; Power system transients; Substations; Switchgear; Transformers;