DocumentCode
853097
Title
Real-time measurement approach for tracking the actual coefficient of ΔV/ΔV10 of electric arc furnace
Author
Guan, Jin-Lung ; Gu, Jyh-Cherng ; Wu, Chi-Jui
Author_Institution
Nat. Taiwan Univ. of Sci. & Technol., Taipei, Taiwan
Volume
19
Issue
1
fYear
2004
Firstpage
309
Lastpage
315
Abstract
This investigation develops a new definition of the voltage fluctuation (ΔV) electric arc furnace. Analysis of voltage flicker spectrum in the 0.25-30-Hz range reveals that the magnitude of each modulation frequency component decreases with frequency, while the standard deviation of each frequency component is high. From the statistics of electric arc furnace real time test data, the loads can be classified as weakly stationary processes, but lack a Gauss probability distribution. Traditionally, the equivalent 10-Hz voltage fluctuation (ΔV10) value can be obtained from ΔV/3.6. However, the real world tests and statistics indicate that the ratios of ΔV/ΔV10 are 1.8, not 3.6.
Keywords
Gaussian distribution; arc furnaces; power supply quality; 0.25 to 30 Hz; Gauss probability distribution; actual coefficient; electric arc furnace; modulation frequency; power quality; real time test data; real-time measurement approach; voltage flicker spectrum; voltage fluctuation; Electric variables measurement; Frequency; Furnaces; Power systems; Probability distribution; Statistical analysis; Statistical distributions; Steel; Testing; Voltage fluctuations;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2003.820182
Filename
1256393
Link To Document