DocumentCode :
853264
Title :
Soil surface potentials induced by Itaipu HVDC ground return current. II. Measurements
Author :
Caroli, C.E. ; Santos, N. ; Kovarsky, D. ; Marques, M.A.M.
Author_Institution :
FURNAS-Centraix Eletricas, Rio de Janeiro, Brazil
Volume :
3
Issue :
3
fYear :
1988
fDate :
7/1/1988 12:00:00 AM
Firstpage :
1211
Lastpage :
1216
Abstract :
For pt.I see ibid., vol.3, no.3, p.1204-1210 (1988). A method used for the measurement of the potential curves in the soil surface is presented, together with its results, obtained at different electrode current levels (199 A, 600 A, and 2300 A). Circuits and instrumentation used are described. Information on measurement noise and on the overall precision obtained is reported. The results are presented in the form of equipotential curves
Keywords :
DC power transmission; soil; surface potential; voltage measurement; 100 A; 2300 A; 600 A; Brazil; HVDC ground return current; electrode current levels; instrumentation; measurement noise; potential curves; precision; voltage measurement; Circuits; Current measurement; Electrodes; HVDC transmission; Instruments; Noise measurement; Power measurement; Soil measurements; Telephony; Voltage measurement;